Plumbing Requirements for Derry Municipal Authority Service Lines and Meter Installations 

 

bullet Service lines will be either type K soft copper or CTS/200 plastic

 

bullet Service lines will be a minimum size of ¾”

 

bullet Fittings will be brass compression or flared

 

bullet No solder joints, glued joints or Tees will be permitted underground

 

bullet Service lines will be a minimum of 4’ deep and be backfilled with select fill or rock dust to a minimum depth of 1 foot over the pipe

 

bullet Service lines other than copper will be copper tubing size (CTS) and have a 200 PSI rating.  Stiffeners must be installed at fittings.  Only brass fittings and stainless steel clamps will be permitted on plastic lines.  Nylon or plastic fittings or connectors are not permitted on plastic service lines

 

bullet All materials must be approved by the Authority

 

bullet Service lines over 100’ in length or residences without basements will require an outside meter setting (meter pit) with a frost free double lid

 

bullet Trenches will remain open until inspected by the Authority

 

bullet No physical connection will be permitted between the plumbing system served from the Authority’s system and private source such as wells or cisterns.  Customers must ensure that no potential cross-connection exists

 

bullet Dual cartridge check valves will be required for back-flow prevention

 

bullet Shut off valves before and after the meter will be required

 

bullet Meters will have outside touch pad readers connected with a wire to the meter

 